Testo 770-3 multimeter and hook clamp meter with Bluetooth 0590 7703
- Can be connected to a smart device via Bluetooth and the free Testo Smart Probes App for remote measurement, data recording, monitoring and creation of measurement reports, including graphs.
- A K-type temperature sensor can be connected.
- TRMS or True root mean square measurement.
- It is not possible to choose wrong settings.
Measuring range for voltage: 1 mV...600 V (DC/AC)
Accuracy for voltage: ±(0.8% of measured value + 3 digits; DC) and ±(1% of measured value + 3 digits; AC)
Resolution for voltage: 1 mV
Measuring range for current (clamps): 0.1...600 A (DC/AC)
Measuring range for current (wires): 0.1...600 μA (DC/AC)
Accuracy for current (clamps): ±(2% of measured value + 5 digits; DC/AC)
Accuracy for current (wires): ±(1.5% of measured value + 5 digits; DC/AC)
Resolution for current (clamps): 0.1 A
Resolution for current (wires): 0.1 μA
Measuring range for resistance: 0.1 Ω...60 MΩ
Accuracy for resistance: ±(1.5% of measured value + 3 digits)
Resolution for resistance: 0.01 Ω
Measuring range for capacitance: 1 nF...60 mF
Accuracy for capacitance: ±(1.5% of measured value + 5 digits)
Resolution for capacitance: 0.01 nF
Measuring range for frequency: 0.001 Hz...10 kHz
Accuracy for frequency: ±(0.1% of measured value + 1 digit)
Frequency resolution: 0.001 Hz
Measuring range for active power: 0.1 W...600 kW
Accuracy for active power: ±(5% of measured value + 5 digits)
Resolution for active power: 0.1 W
Measuring range for reactive power: 0.1 var..600 kvar
Accuracy for reactive power: ±(10% of measured value + 5 digits)
Resolution for reactive power: 0.1 var
Measuring range for apparent power: 0.1 VA...600 kVA
Accuracy for apparent power: ±1 digit
Resolution for apparent power: 0.1 VA
Measuring range for direct current/DC power: 0.1 W...600 kW
Accuracy for power DC/DC: ±1 digit
Power resolution for DC: 0.1 W
Measuring range for power factor: -1.00...+1.00
Accuracy for power factor: ±(10% of measured value + 5 digits)
Resolution for power factor: 0.01
Measuring range for temperature (for K-type sensor): -20...+500°C
Accuracy for temperature in the range 0...+100°C (for K-type sensor): ±1°C
Temperature resolution (for K-type sensor): 0.2°C
Operating temperature: -10...+50°C
Relative air humidity of use: 0...80%rM
Storage temperature: -15...+60°C
Batteries: 3xAAA finger batteries (included)
Dimensions: 249×96×43mm
Safety standard: CAT IV 600 V; CAT III 1000V
Weight: 378g
Measuring cables included.